Aluminium Stranded Conductor: What to Check and Test Before You Buy

Overhead aluminium stranded conductor carries your power from the source to the load, and its resistance, strength and construction decide how much energy you lose and how long the line survives wind, heat and tension. This guide explains the WAPDA/NTDC specification P-63 in plain language for housing societies, builders, industries and government departments. It is a free public guide. We do not sell conductor.

What is an aluminium stranded conductor?

An aluminium stranded conductor is an overhead line conductor made only from round, hard-drawn aluminium wires twisted together in concentric layers. It is often called AAC (all aluminium conductor). The wires are the same nominal diameter, a conductor has seven or more of them, and each layer is twisted in the opposite direction to the one beneath. The outer layer is right-hand lay.

Specification P-63 covers exactly this product. It was first approved on 14 February 1970, revised on 20 September 1979 and revised again on 8 August 2007. It is a P-specification, the older WAPDA numbering explained on the Chief Market main page, and it is based on IEC recommendation 207.

Important scope note: P-63 does not cover ACSR (steel-reinforced) conductors such as Rabbit, Dog or Ospray. Those have a steel core and a separate specification. If your order says ACSR, this guide is not the right checklist. If your order says Gant, Ant, Wasp, Arbutus, Hawthorn or Coreopsis, it is.

The six standard sizes

P-63 standardises six conductors for NTDC/WAPDA use, each with a code word. Pick one below. The page shows the values printed in the specification and recalculates them from the specification’s own constants. When the two agree, the conductor data is internally consistent.

ItemPrinted in P-63Recalculated

Where the aluminium is used

  • Gant (25 sq mm, 7/2.21 mm): short, light spans and small secondary connections.
  • Ant (50 sq mm, 7/3.10 mm): light distribution and service lines where spans are short.
  • Wasp (100 sq mm, 7/4.39 mm): a common distribution size for medium feeders.
  • Arbutus (400 sq mm), Hawthorn (600 sq mm), Coreopsis (about 810 sq mm): heavy conductors used mainly for substation busbars and large connections. P-63 names Coreopsis as the busbar conductor for 500 kV, 220 kV and 132 kV switchyards.

Which size you need is a design decision based on current, voltage drop, span and sag. A conductor that is too small saves cost on day one and wastes it as loss every hour afterward. Ask your design engineer for the calculation instead of picking by price.

Material: what the aluminium must be

P-63 sets the electrical and physical constants that every test is judged against.

  • Purity: not less than 99.5 percent aluminium by weight.
  • Resistivity: maximum 0.028264 ohm sq mm per metre at 20°C. This value is also the standard for calculations.
  • Density: 2.703 kg per cubic decimetre at 20°C.
  • Temperature coefficient of resistance: 0.00403 per degree centigrade (constant mass, at 20°C).
  • Condition: hard-drawn wire, clean, smooth and free from harmful defects before stranding.

Purity is the quiet quality factor. Recycled or impure aluminium raises resistivity, so a conductor can have the right diameter and still lose more energy than designed. Only a resistivity test and the base-rod check prove it. Appearance does not.

Wire strength: Table I explained

P-63 gives a minimum ultimate tensile stress for each wire diameter, once before stranding and once after. Smaller wires are drawn harder and are stronger per unit area. For a wire with an intermediate diameter, clause 5.3 says to use the value for the next larger diameter in the table.

Wire dia (mm)Before stranding (kg/sq mm)After stranding (kg/sq mm)Wire dia (mm)BeforeAfter
1.2520.419.43.5016.715.9
1.5019.718.73.7516.515.7
1.7519.218.24.0016.315.5
2.0018.817.94.2516.315.5
2.2518.417.54.5016.215.4
2.5018.017.14.7516.215.4
2.7517.616.75.0016.215.4
3.0017.216.33.2516.916.0

Example: the Wasp wire is 4.39 mm. That is between 4.25 and 4.50, so the next larger diameter, 4.50 mm, applies: at least 16.2 kg/sq mm before stranding and 15.4 kg/sq mm after. Stranding twists the wires and slightly lowers the strength of each one, which is why the second column is lower.

Whole-conductor strength. For conductors with up to 37 wires, P-63 takes 95 percent of the sum of the individual wire strengths. For more than 37 wires (Hawthorn and Coreopsis, 61 wires each), it takes 90 percent. A tensile test on a complete conductor needs a sample at least 5 metres long with suitable end fittings.

Construction: stranding, lay and joints

Wire dimensions

  • Wire diameter tolerance is plus or minus 1 percent, with a minimum of 0.025 mm.
  • The wire cross-section must not depart from a circle by more than a 2 percent tolerance on the nominal diameter.
  • Diameter means the mean of two measurements at right angles at the same cross-section.

Lay ratio

  • Lay ratio is the length of one full turn of a wire divided by the outer diameter of that helix.
  • For the first layer of 6 wires the allowed range is 10 to 14 (7-wire conductor) up to 10 to 17 (37 and 61 wires).
  • Successive layers have opposite lay, and the outer layer is right-hand.
  • No layer may have a greater lay ratio than the layer beneath it.

Joints in wires

  • A 7-wire conductor (Gant, Ant, Wasp) may have no joint in any wire, except in the base rod before final drawing.
  • Conductors with more than 7 wires may have wire joints, no two closer than 15 metres, made by resistance or cold-pressure butt welding.
  • Resistance-welded joints must be annealed for at least 200 mm each side.
  • Joint wires need not meet the full mechanical or electrical limits.

Tests: what each one proves

P-63 lists five tests for both the manufacturer’s own quality control and the buyer’s acceptance: visual inspection, verification of dimensions, tensile test, wrapping test and resistivity test.

TestMethod in P-63What you learn
Visual inspectionRoutine check of wires and complete conductorSurface damage, loose or crossed wires, kinks, dirt, uneven stranding.
Verification of dimensionsWire and conductor diameters against Table II and the tolerancesWhether you receive the cross-section you are paying for.
Tensile testOn wire before and after stranding. Automatic machine: jaws not faster than 100 mm per minute. Hand lever: 90% of load applied quickly, the last 10% in about 15 seconds, about 20 seconds in totalWire strength against Table I, and whether stranding damages the wire.
Wrapping testWire wrapped around a mandrel equal to its own diameter in a close helix of eight turns. Six turns are unwrapped and wrapped againDuctility. The wire must not break or crack. Brittle or poorly processed aluminium fails.
Resistivity testResistance measured to 1 part in 1000 at 10 to 30°C, then corrected to 20°CPurity and conductivity. The result must not exceed 0.028264 ohm sq mm per metre.

Before manufacture begins, the base rod is tested for resistivity: one specimen from every 10 coils, and non-conforming material must not be used. Tensile and wrapping tests on finished wire (before stranding) cover at least 10 percent of the wire lengths in a consignment.

Correct a resistance reading to 20°C

Resistance changes with temperature, so a lab reading is corrected to 20°C before it is compared with the limit. P-63 gives the formula R20 = RT divided by (1 + 0.00403 × (T minus 20)). Try it with a reading taken between 10°C and 30°C.

Test temperature must lie between 10°C and 30°C. The resistivity limit applies to the value corrected to 20°C.

How a lot is accepted or rejected

  • The manufacturer divides the consignment into lots of reasonably uniform quality, made at the same time under the same conditions. A lot holds up to 150 lengths.
  • From each lot, whatever its size, wire samples are taken at random from 10 lengths of stranded conductor, from every strand in each selected length.
  • If at most one specimen fails a test, the sample is acceptable for that test.
  • If two specimens fail, a further sample is taken and that test is repeated. If there are no further failures, the sample is acceptable.
  • If three or more specimens fail any test, the whole lot is rejected.
  • The manufacturer must give the inspector all test facilities and help, free of charge.

Because every lot is sampled the same way, a buyer who asks for lot-wise inspection gets the same protection on a 10-reel order as on a 100-reel order. Insist that the lot number appears in the test report.

What to check before buying

Ask the manufacturer for

  • A certificate that the conductor conforms in all respects to P-63 (clause 8.6).
  • Test records for the lot: base rod resistivity, wire tensile and wrapping tests, resistivity, dimensions.
  • Proof of aluminium purity of at least 99.5 percent from the rod supplier.
  • The record of production lots, so lots can be identified (clause 10.1).
  • Calibration certificates for the tensile machine and resistance bridge.
  • Written confirmation of the edition: P-63:2007 or later, “amended to date”.

Check on delivery

  • Wooden reels of sound construction with heavy lagging and two steel straps.
  • Reel markings on both sides: manufacturer, conductor designation, consignee address and purchase order number, reel serial number.
  • A metal plate nailed to the reel with size, net, tare and gross weight, length on the reel and serial number.
  • An arrow showing the direction of rolling on both sides.
  • Length per reel within plus or minus 5 percent of the specified length, and no more than 5 percent of an order supplied in random lengths, none shorter than one third of the nominal length.
  • Conductor wound tightly, with no loose or damaged outer wires.

Points to clarify with the issued specification

Our reading of the document found these inconsistencies

  • Edition label. The cover says P-63:2007, but the page heading still reads P-63:79. Confirm which edition your purchase order names.
  • Coreopsis row in Table II. The area is printed as 1075.06 sq mm and the strength as 13670 kg. Sixty-one wires of 4.11 mm give about 809 sq mm, which matches its nominal size, resistance and weight. By clause 6.4.4 the minimum strength would be about 11,870 kg. Verify these two values with the official copy before using them in an order.
  • Linear expansion. Clause 4.3 repeats the density figure where the coefficient of linear expansion should appear. Ask your design engineer for the correct coefficient.
  • Clause reference. The tensile test clause (7.1.4) points to clause 4.2, but the strength values are in Table I of clause 5.2.
  • Clause 1. It describes switchyard busbar requirements (short-circuit withstand and current ratings for 500, 220 and 132 kV). It is not relevant to ordinary distribution conductor.

None of this changes the conductor tests. It means you should write the order precisely and ask the issuing office for any corrected edition.

Red flags to watch for

  • A test report that shows only dimensions and weight, with no resistivity, tensile or wrapping results.
  • Test results that show the wire exactly at the limit on every sample. Real production varies, so ask to see the spread.
  • A 7-wire conductor with any wire joint, or joints closer than 15 m in larger conductors.
  • Outer layer with left-hand lay, or inner layers with a larger lay ratio than the layer beneath.
  • Diameter or weight per kilometre noticeably below the printed values, which may indicate under-sized wire.
  • Reels that are damaged, unmarked, or missing the metal data plate.
  • A manufacturer unable to show the base-rod resistivity record.

Manufacturer track record from our inspections

This table is completed only from Chief Consultant’s own inspection records. A blank means we have not verified the point.

ManufacturerSizes inspectedMeasured resistivityWire strength vs Table ILot rejectionsOur note
To be added–––––

Need advice for your project? Contact Chief Consultant with the conductor size, quantity and site, and our engineers will guide you.

Frequently asked questions

What is the difference between aluminium stranded conductor and ACSR?
Aluminium stranded conductor uses aluminium wires only. ACSR has a steel core for extra strength and is covered by a different specification.

What is the maximum resistivity allowed?
0.028264 ohm sq mm per metre at 20°C.

How many wires does a Wasp conductor have?
Seven wires of 4.39 mm, giving about 106 sq mm, a diameter of 13.17 mm and a printed strength of 1633 kg.

Can I accept a lot if one specimen fails?
Yes for that test, if at most one specimen fails. Two failures require a further sample. Three or more failures reject the lot.

Are joints in the wires allowed?
Not in 7-wire conductors. Larger conductors may have butt-welded joints at least 15 m apart.

A Note on Accuracy

This page summarises specification P-63:2007 for general guidance. The official specification and your purchase order prevail. Check that the edition is current before ordering.